Operating instructions
Contents
Unset system indications - - - - - - - - - - Set System indication - - - - - - - - - - - Access codes - - - - - - - - - - - - - - - How to operate Personal Attack - - - - - How to unset system in alarm - - - - - - Programs 1, 2 and 3 - - - - - - - - - - - - How to set the system (on program 1) - - Push to Set Switch - - - - - - - - - - - - - Keyswitch Set - - - - - - - - - - - - - - - Faults during setting - - - - - - - - - - - - How to unset the system (turn off) - - - - How to set program1,2 or 3- - - - - - - - How to Quick set - - - - - - - - - - - - - How to Omit zone(s) on setting system - - Fire Alarm - - - - - - - - - - - - - - - - How to set Chime zone - - - - - - - - - - Operator's Program mode - - - - - - - - - To exit operation at any time - - - - - - - - How to enter Operator's program mode - How to view the event log - - - - - - - - - How to create/omit User 2 code - - - - - - How to change current user code - - - - - How to create/change/omit the Duress code How to carry out Alarm and Walk tests- - Servicing organisation details - - - - - - - - Quick Reference - - - - - - - - - - - - - - 1 1 2 2 2 2 3 3 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 7 7 8
Accenta/Optima G3 Intruder system
How to unset system in alarm
Enter your code. Entering the code will turn the alarm off and the cause of the alarm will be displayed. After investigation press Reset to clear the indication.
n n n n
Bell
Alarm
FIRST ZONE IN ALARM OTHER ZONES IN ALARM
Investigate the Alarm
Reset
ALL ZONE
Strobe Off
Day
Access codes
Note: If the alarm indication does not clear, then the system may need to be reset by the installation engineer, contact you installer for further information.
Programs 1, 2 and 3 Access codes
There are two User codes used in the system, all are 4 digit and can be set to any number from 0000 to 9999, signified by:
n n n n
The user 1 and 2 codes have the same operation for testing, Setting and Unsetting, but user 1 code which is usually considered to be the Managers code has the authority to add, change or delete the user 2 code and Duress code.
The panel uses 3 Part Set routines known as Programs. In each Program the exit mode can be changed and the zone may be set up to have a different function. The examples below show how 3 typical Programs could be used in a house. Program 1 To arm all of the zones and become Set as the user leaves the property and closes the final door. Program 2 To protect the perimeter of the property in the evening and become Set after say 20 seconds. Program 3 To protect the downstairs areas of the house at night and become Set silently. The above are purely examples. The installer has the ability at the programming stage to configure all the circuits to the customer's exact requirements.
ÿ ÿ
User 1 code - 0123 factory set User 2 code - not programmed.
How to operate Personal Attack
Personal Attack buttons on the keypad are used to activate the alarm, irrespective of whether the system is armed or not. Press Simultaneously: 9 4
2
4PI175 issue 1_6/01
Accenta/Optima G3 intruder system
Operating instructions
How to set the system (on program 1)
The green Day indicator should be showing. Day Enter your code number and check n n n n that the system is clear (none of the 10seconds Exit beep insistent beeps zone indicators are showing). The Day sounder will now produce an exit o/p ARC beep tone and you Set output should leave by the approved route. The system will Set as the beep tone stops.
How to unset the system (turn off)
On entering the premises an entry beep tone comes on. Enter your code, the green Day indicator is lit. The system is unset and disarmed.
Entry beep Day
Acknowledge Day
Push to Set Switch
In some systems a Push to Set switch may be fitted outside the premises near to the main exit door. This should be used to complete the setting procedure once the building has been vacated. As the switch is operated, the exit beep tone will stop and a chime tone will be produced to acknowledge setting.
o/p ARC Unset output
How to set program1,2 or 3
The green Day indicator should be showing. Day Enter your code number and the n n n n exit beep tone will start. Press Exit beep the Prog key and ZONE 1-3 Prog Exit beep the exit tone will stop. Press 1, 2 2 Or 3 1 or 3 for the required 10 seconds Exit beep insistent beeps program, the sounder will Day beep to o/p ARC acknowledge the Set output program number. The exit beep tone will start and you should leave by the approved route. The system will Set as the beep tone stops. It is important that you follow the correct procedure when setting the system. After leaving the protected area it is absolutely essential that you wait until the exit tone stops, before assuming the system has set.
Keyswitch Set
Your system may have been fitted with a remote keyswitch. This can be used as an alternative to arming the system with a code and will set Program 1. Where a keyswitch is used it may be necessary on occasions to allow it to catch up with the system. For example if the alarm was set with a code, to Unset with the keyswitch, it would have to be momentarily turned to Set then returned to Unset.
Faults during setting
If the system is not clear when you try to Set it, the sounder will produce an open zone tone and the fault will be displayed. Either re-enter your code to turn off and investigate or omit the faulty zone(s) from the system.
4PI175 issue 1_6/01
3
How to set the system (on program 1)
n
n
n
n
Operating instructions
Accenta/Optima G3 Intruder system
How to Quick set
During the exit period (on entering User code) Day the system may be Set Set the system or quickly by pressing Set. This removes the exit time Set a Program period.
Set
5 seconds insistent beeps Day
How to set Chime Zones
Example: To set zone 3 and 4 to chime, Press:
Chime
3
Day
4
Reset
If you omit zones and require Quick Set, you will need to press Set twice.
Chime
Timeout after 5 seconds if no selection is made
Day Chime
o/p ARC Set output
0
Deselect all zones (Factory default - no chime) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Appropriate Zone indicator is lit to show chime zone(s)
Zone n Chime selected Zone n Chime deselected
How to Omit zone(s) on setting system
Press number button to select / deselect Zone Chime
1 2 3 4 5 6 7 8
During the exit period after entering User code and selecting a Day program press Set the system or Set a Program and while theOMIT, the exit tone will stop and zones system is setting: that are about to be Omit ZONE(S) TO BE ARMED armed will be displayed. Key in Exit beep the zone number(s) to be omitted which Press the zone(s) n to be omitted will flash to confirm selection. Zone ZONE(S) TO BE OMITTED indicators which show steady are still Set about to be armed. 10 seconds Exit beep insistent beeps When the selection is complete press Day Set and the exit tone o/p ARC will start. Set output If a zone refuses to be omitted, it may be because the engineer has programmed the panel to prevent you from turning off the zone. If in doubt ask your installer for advice.
How to Quick set
Reset
Leave chime mode
Day
Fire Alarm
The fire zone will operate on detection of a fire, whether the system is Set or Unset, when configured as a 24 hour zone, and cause a distinctive internal sounder tone. The external sounders will pulse on and off at 2 second intervals and all keypad indicators will flash to attract attention.
Chime is a low security monitoring system for use when the system is Unset. When a zone that is set to chime is operated, the internal sounder will produce a low volume two stage warning tone and the Zone indicator will show. The indicator may be cancelled by pressing Reset. Chime is particularly useful in a shop to warn of a customer presence or in a house to warn that a door or particular area has been accessed. Any zone may set to be on or off chime by pressing the CHIME key and then keying in the required zone number(s). Key 0 to cancel all zones from chime. After a few seconds the system will automatically return to the Day mode.
4PI175 issue 1_6/01
4
Accenta/Optima G3 intruder system
Operating instructions
Operator's Program mode
The information below shows the programmable options available and how to change them. Once the programming mode has been accessed, each section may be changed in any order. As each operation is completed the system will automatically return to top level of program mode.
How to view the event log
The panel can hold up to 8 previous events which can be scrolled automatically or manually. The automatic scroll starts with the newest event ( number 8) to the oldest one ( number 1).
Example: To view up to 8 previous events and thereafter to stop the event scroll, Press: Prog 0 1 2 3 Chime
Reset
Note: When programming the system should be in the Day mode, with the Day and Power indicators lit.
Enter Operator's program mode
Chime
View the event log
Tamper
To exit operation at any time
On pressing the Reset key you will quit the current level of operation.
Reset
Automatic event scroll Starting from event 1 to 8 To manually scroll View event 1 1 (oldest event)
2 3
Zone, PA and Tamper indicators will be lit to show zone in alarm. Flashing indicates the first zone in alarm. Day indicates status of panel at the time of alarm
Quit the current function Leave Engineering menu Down one menu level
View event 2 View event 3 View event 4 View event 5 View event 6 View event 7
How to enter Operator's program mode
To enter the Operator's program mode the system should be in Day Prog mode with the Day and ZONE 1 - 8 Power indicator lit. Momentarily On
0 1 2 3
4 5 6 7
8 View event 8 (Newest event) Chime Resume automatic scroll
Acknowledge
Tamper
Day
Reset
Stop event scroll / view Leave program mode
Day Acknowledge Tamper
Tamper
4PI175 issue 1_6/01
5
Operator's Program mode
Operating instructions
Accenta/Optima G3 Intruder system
How to create/omit User 2 code
User 1 code which is usually considered to be Example: To create user 2 the Managers code 4567, Press: code has the Prog 0 1 2 3 7 authority to add, change or delete Reset 4 5 6 7 the user 2 code.
Enter Operator's program mode Change / omit User code 2 7 (By user 1 only)
Attack
How to create/change/omit the Duress code
The Duress code is used in a hold up situation where there is pressure to Set or Unset the system. Entry of the code will allow the system to work normally but also generate a silent PA type alarm by operating the PA communicator output. The duress code in not preprogrammed and can be created.
Example: To createduress 5555, Press:
Prog
ZONE 1-4
0 5
1 5
2 5
3
Reset
9
How to create/omit User 2 code
n
n
n
n New code
5
NOTE - The sounder will produce a flat beep if code is rejected.
Or
Omit
To omit the user 2 code
Enter Operator's program mode Change / Omit the Duress 9 Code (By user 1 only)
Attack
Rising beeps ZONE 1-4 Attack
ZONE 1-4
Reset
Leave program mode
Day Acknowledge Tamper
n
n
n
n
New duress code
How to change current user code
Rising beeps
You can change the current user 1 or user 2 Example: To change user 1 code for security code from 0123 to 7777, Press: reason.
Prog
ZONE 1-4 Attack
0 7
1 7
2 7
3
Reset
8
Reset
Leave program mode
Day Acknowledge Tamper
7
Enter Operator's program mode
8
Change the code of Current user (either User 1 or User 2)
Attack
ZONE 1-4
n
n
n
n
Current user new code
NOTE - The sounder will produce a flat beep if code is rejected.
Rising beeps ZONE 1-4
NOTE - Factory default code for User 2 is not programmed
Attack
Reset
Leave program mode
Day Acknowledge Tamper
6
4PI175 issue 1_6/01
Accenta/Optima G3 intruder system
Operating instructions
How to carry out Alarm and Walk tests
The alarm test function allows you to test the Strobe, Bell, Low and high volume sounders of the system. The walk test function allows each detector to be checked in order to verify that they are functioning correctly.
Example: To start bell test and thereafter to stop bell test. Prog 0 1 2 3 0 3 0 Reset Reset Enter Operator's program mode
0 Alarm test
Attack
Press zero to turn off options 2,3,4 and 5 before selecting a new one
2
Strobe test
Strobe On Bell on
Day
Day
3 Bell test 4 5 6
Low volume sounder High volume sounder Walk test
internal low volume sound internal high volume sound Strobe
Day
Day
Strobe On
Day
x1 for zone 1 x2 for zone 2 | x4 for zone 4 flat x1 for zone 5 flat x2 for zone 6 | flat x4 for zone 8 Rapid for PA Rapid for Tamper
Appropriate zone lights are lit(latched) Zones
0 OFF
Day
Reset
Attack
Reset
Exit current level
Attack
Leave program mode
Day Acknowledge Tamper
Tamper
Servicing organisation details
Servicing organisation name: ______________________________________ Telephone number: ______________________________________ Date of installation: ______________________________________ Account Number: ______________________________________ Installation Date: ______________________________________
Bell Time:_____________________________ Bell delay______________________________ Area protected Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 T = Timed (Entry/Exit - Zone) TI = Time Inhibited (Access zone to keypad) I = Immediate (All zones armed to give full alarm) Program 1 Program 2 Program 3
4PI175 issue 1_6/01
7
How to carry out Alarm and Walk tests
Quick Reference
8
To Set the system (Program 1)
Day Entry beep Day Day Day
To Set a Program
n n n n
To Un-set the system To Quick Set the system
Day
To Reset Alarm state
To Omit zones on Setting system
n
n
n
n
Bell
Alarm FIRST ZONE IN ALARM
Quick Reference
n
Exit beep
n n
Exit beep Acknowledge Day Day
Reset
n n
Set
Omit
OTHER ZONES IN ALARM 5 seconds insistent beeps
n n n
Prog
ZONE 1-3
Set the system or Set a Program
Operating instructions
Exit beep 10seconds insistent beeps
Set the system or Set a Program and while the system is setting:
ZONE(S) TO BE ARMED Exit beep
1
Or
2 3
10 seconds insistent beeps Exit beep Day
Day
Investigate the Alarm
ALL ZONE
o/p ARC Set output o/p ARC Set output
Day
o/p ARC Unset output
o/p ARC Set output
n
Press the zone(s) to be omitted
ZONE(S) TO BE OMITTED
Strobe Off
Set
The panels conform to the requirements of the European EMC and Low Voltage directives, and carries the CE mark
Operator's program mode menu map
Operator's Progam Mode Prog
n 8
Chime
Chime
n
n
n
To exit Operator's program mode
Reset
To set Chime zone
Chime
Exit beep
Alarm 0 test
7
Change / omit User code 2 (By user 1 only) Change the code of Current user (either User 1 or User 2) View the event log
n n n n n
Reset
10 seconds insistent beeps
2
Strobe test
Omit
n
n
n New code
Automatic event scroll Starting from event 1 to 8 For manual scroll
1
1
Zone to chime
Day
3 Bell test
Reset
To omit the user 2 code
Leave program mode Leave program mode View event 1 (oldest event)
8
Reset
o/p ARC Set output
4 5 6 0
Reset Reset
Low volume sounder High volume sounder
Change / Omit 9 the Duress Code (By user 1 only)
n n n n
8 View event 8 (Newest event)
Chime
Normal indications of an Unset system
Resume automatic scroll
Day Power
Walk test Press zero to turn off options 2,3,4 and 5 before selecting a new one
Leave program mode Exit current level Leave program mode Quit the current function Leave program menu Down one menu level
Alarm indications
Reset
Reset
Stop event scroll / view
Reset
Bell On
Leave program mode
Strobe
Alarm
Accenta/Optima G3 Intruder system
4PI175 issue 1_6/01
Reset
ADE ACCENTA G3 , ADE OPTIMA G3, , Safety & Domotic.
Detailed instructions for use are in the User's Guide.
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual ADE ACCENTA G3 , ADE OPTIMA G3.
ADE offer a product for which we do not have the user manual? Let us know what you are looking for: user manual, user guide, instructions, owner's manual, online manual, user's manual, users manual, users guide, owner manual, owners manual, user's guide, handbook, instructions for use, instruction manual, operation manual, operating instructions, installation guide, quick start guide, quikstart guide, getting started, installation instructions, installation guide,mounting instruction, assembly instrucions, fixing instructions, use instruction, schematics, operating manual, feature sheet, data sheet, booklet, service manual, use and care guide, installation manual, installation software, RTFM.
Diplodocs allows you to download user manual ADE ACCENTA G3 , ADE OPTIMA G3, user guide ADE ACCENTA G3 , ADE OPTIMA G3, instructions ADE ACCENTA G3 , ADE OPTIMA G3, owner's manual ADE ACCENTA G3 , ADE OPTIMA G3, online manual ADE ACCENTA G3 , ADE OPTIMA G3.
Access web reviews
 |
This site allows you to download and store : user manual, user guide, instructions, owner's manual, online manual, user's manual, users manual, users guide, owner manual, owners manual, user's guide, handbook, instructions for use, instruction manual, operation manual, operating instructions, installation guide, quick start guide, quikstart guide, getting started, installation instructions, installation guide,mounting instruction, assembly instrucions, fixing instructions, use instruction, schematics, operating manual, feature sheet, data sheet, booklet, service manual, use and care guide, installation manual, installation software, RTFM.
|
|
Copyright © 2005 - 2008 - Diplodocs -
All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.
| |