Download user guide, user manual, owner manual and instructions guide
5 600 brands
1 870 000 user's guides
Search a brand
Advanced Search



Our partners wish to propose you the following products


Visit APC official site

User manual APC BACK UPS BR1300LCD

Diplodocs help download the user guide APC BACK UPS BR1300LCD.

Download the user manual APC BACK UPS BR1300LCD  
Download the complete
user guide (600 Ko)
Need help, support, reviews, tips or troubleshooting for your APC BACK UPS BR1300LCD products ?



Preview of the first 3 pages of manual

You either have JavaScript turned off or an old version of Adobe Flash Player
Get the latest Flash Player.
User guide APC BACK UPS BR1300LCD

Detailed instructions for use are in the User's Guide.

2 ® 1 CONTENTS RJ-11 RJ-45 RJ-11 RJ-45 2 CONNECT BATTERY CARTRIDGE* w w w.apc.com Back UPS® BR1300LCD Back-UPS® BR1500LCD Back UPS® BX1300LCD Back-UPS® BX1500LCD User's Manual USB RJ-45 1 Coax Coax 2 Æ Note: This diagram is also used for battery cartridge replacement. 3 OPERATING ENVIRONMENT 4 CONNECT EQUIPMENT / POWER FAX 3 5 CHECK BUILDING WIRING FAULT INDICATOR If the rear panel Building Wiring Fault (red) indicator is lit, a potential shock hazard exists due to one of the following conditions: · Open or high resistance ground · Hot and Neutral polarities are reversed · Overloaded neutral circuit Improper building wiring should be corrected by a qualified electrician. Do not use the Back-UPS until the condition that caused the fault is corrected. Note: Improper building wiring will not prevent the BackUPS from operating, but it will limit its protection capability. 6 CONNECT MODEM/PHONE/Network and TVSS Ground If needed, the Back-UPS features a TVSS ground screw for connecting the ground lead of any additional stand alone surge suppression devices, such as an APC ProtectNet product; or any electronic device with an external ground connection. 8 CONNECT DATA LINE AND INSTALL SOFTWARE ON COMPUTER (Optional) RJ-45/ RJ-11 RJ-45/ RJ-11 RJ-45/ RJ-11 RJ-45/ RJ-11 From stand alone data line surge suppressor or electronic device CABLE IN To USB Port USB RJ-45 CABLE OUT Building Wiring Fault To USB Port 32 - 104oF (0 - 40oC) Computer Printer or Scanner Phone Jack External Disk or CD / DVD Drive Monitor Computer Modem Port OR Phone or Fax 2 CABLE IN CABLE OUT 7 CONNECT COAXIAL CABLES Coaxial Cable CABLE IN From Cable Provider To Cable Modem 1. Insert CD into computer, and on-screen instructions should appear automatically. Follow instructions to complete the installation. Note: if the on-screen instructions do not appear automatically (Autoplay is disabled), then perform steps 2 and 3 below. 2. On the computer desktop of the display, double-click on My Computer. 3. Double-click on the CD-ROM drive icon, and follow the on-screen instructions. Installation of the supplied software is the only way to take advantage of the auto shutdown capabilities that Back-UPS offers. Follow the on-screen instructions. 30 cm To 120 VAC Wall Outlet Building Wiring Fault Building Wiring Fault Indicator CABLE OUT Building Wiring Fault Coaxial Cable LCD INDICATORS and CONTROLS SUMMARY 9 SWITCH ON THE BACK-UPS Note: Allow the Back-UPS to charge for a full 16 hours prior to using it. Press the front panel Power ON/OFF switch, and observe that the following events occur after you press and release the switch: · The LCD turns on (is back lit). · The ON LINE indicator flashes. · The ON BATT indicator lights and flashes while a self-test is being performed. · When self-test has successfully completed, only the ON LINE indicator will be lit. · If the internal battery cartridge is not connected (see Step 2 above), the ON BATT indicator will flash. The Back-UPS will also emit a chirping sound. The red, back lit liquid crystal display (LCD) on the front panel of the Back-UPS displays realtime system status messages, system faults and warnings, LOAD Capacity, and Battery Charge level. Two switches are provided on the front panel, the power ON/OFF pushbutton switch on the left, and the DISPLAY/HOLD TO MUTE pushbutton on the right. LOAD ON LINE DISPLAY DISPLAY/HOLD TO MUTE button - is used to display status messages, system faults and warnings, and to perform various operations, such as alarm mute mode, AVR (automatic voltage regulation), and full time display mode. The various messages, warnings, system faults, and operations are described in greater detail on Page 2. ON LINE - is lit whenever utility power is supplied to power the equipment connected to the Back-UPS. ON BATT - the On Battery symbol is lit whenever battery backup power is used to power equipment connected to the Back-UPS. Four Beeps Every 30 Seconds - this alarm sounds whenever the Back-UPS is running on battery (ON BATT). You should consider saving any work in progress. Continuous Beeping - this alarm sounds whenever a low battery condition occurs, and battery run-time is very low. Promptly save any work in progress, exit all open applications, and shut down the operating system, computer, Load Capacity - this indicator consists of a bar containing five blocks. When only one or two of the blocks are filled (lit), the unit LOAD is at less than half capacity. LOAD However, when all five blocks are filled, the LOAD is at full capacity. If the LOAD exceeds the unit's rated capacity, the Overload symbol on the bottom of the display will flash off and on. Battery Charge - this indicator consists of a bar with five blocks. When all five blocks are filled, the battery is fully charged. When only one block is filled (lit) the battery charge is low. The word LOW and the Battery Capacity indicator bar both flash off and on. Overload - is lit whenever power demand exceeds the capacity of the Back-UPS. It is displayed in both ON LINE mode, and ON BATT mode. AVR When lit, it indicates automatic voltage regulation (AVR) is in "Boost mode". AVR is covered in greater LOAD Capacity SENSITIVITY LOW ON BATT detail on Page 2. System Faults - when a fault occurs, this symbol and the fault number (F01 - F09) will flash off and on. The nine fault messages are described further on Page 2. Self-Test mode - can be run at any time when in ON LINE mode. Self-test is covered in greater detail on Page 2. Mute mode - the audible alarm (beeper) can be muted (turned off), which is indicated by a line through the beeper symbol. Mute mode is covered in greater detail on Page 2. Sensitivity mode - this allows you to go into sensitivity programming mode, and using the DISPLAY button you can select the LO, MID or HIGH sensitivity range. Sensitivity mode is covered in greater detail on Page 2. Full Time Display mode - this mode allows you to set the LCD to full time display mode using the DISPLAY button. This mode is covered in greater detail on Page 2. Reset switch - this switch is located on the rear of the Back-UPS, just above the fans, as shown in the figure in Step 4. 990-4991 ESTIMATED RUN TIME IN MINUTES Battery Charge IN OUT V kW Hz % System Faults AVR SEE MANUAL System Status DISPLAY HOLD TO MUTE Continuous tone - this alarm sounds whenever the battery backup outputs are overloaded. Overload mode is covered in greater detail on Page 2. Replace battery - this is lit whenever the battery is near the end of its useful life, or if the battery is not connected. A battery nearing the end of its life should be replaced. LOAD ON LINE LOW ON BATT SENSITIVITY ESTIMATED RUN TIME IN MINUTES IN OUT V kW Hz % AVR SEE MANUAL DISPLAY HOLD TO MUTE Power ON/OFF switch - is used to turn input power on and off. It is also used to initiate self-test, to go into Sensitivity mode, and it is used with the DISPLAY button to reset the Event Counter. Chirps for 1 Minute every 5 hours - this alarm sounds whenever the battery fails the automatic diagnostic test. ON-LINE MODE Display Selection When you are in ON-LINE mode, and press the DISPLAY button, you will rotate through the following seven groups of displays and messages. When you press the DISPLAY button the first time, the LCD is back lit, and the input voltage (IN) default screen is displayed, in this example 110 V is displayed. When you press the DISPLAY button a second time, the power EVENT counter is displayed, as shown below. To reset the counter, press and hold the DISPLAY button, and press the power ON/OFF button. LOAD ON LINE ON-LINE MODE (Continued) When you press the DISPLAY button a seventh time the ON BATT output (OUT) frequency is displayed, in this example it is 60.0 Hz. V LOAD ON LINE BATTERY MODE (Continued) When you press the DISPLAY button a sixth time, the battery backup LOAD is displayed as a percentage (%); in this example it is 82%. ON BATT OTHER STATUS INDICATORS LOAD Self-Test To initiate self-test mode, press the power ON/OFF button, and hold it in for ONE second. The AC plug symbol (ON LINE) flashes off and on during self-test mode. % Flashing LOAD ON LINE IN IN V OUT Hz DISPLAY BATTERY MODE Display Selection When you are in battery (ON BATT) mode, and press the DISPLAY button, you will rotate through the following seven groups of displays and messages. LOAD When you press the DISPLAY button a seventh time the ONLINE output (OUT) frequency is displayed, in this example it is 60.0 Hz. ON BATT LOAD Mute ON BATT LOAD OUT ON BATT Hz LOAD ON LINE When you press the DISPLAY button the first time, the LCD is back lit, and the default screen (ESTIMATED RUN TIME IN MINUTES) is displayed, in this case it is 18 minutes. ESTIMATED RUN TIME IN MINUTES WARNINGS Warning 1 - Online Overload This warning indicates that there is an ONLINE overload condition at 1.25 kW, indicated by the flashing overload icon. ON LINE When you press the DISPLAY button a second time, the power EVENT counter is displayed, as shown below. To reset the counter, press and hold the DISPLAY button, and press the power ON/OFF button. DISPL AY DISPLA Y LOAD kW LOAD ON LINE LOAD Flashing This feature allows you to mute the audible alarm (the beeper) for a single display and message. To mute the audible alarm, the unit should be on battery, or the ESTIMATED RUN TIME IN MINUTES "speaker" symbol is displayed. Press the DISPLAY/ HOLD TO MUTE button for ONE second, the alarm (beeper) is toggled, and the "speaker-NOT" symbol (speaker with a line drawn through it) is displayed on the screen. To enable an audible alarm that has been muted, perform the same steps that were used for muting the alarm. The alarm (beeper) can also be muted all the time. With the speaker or speaker-NOT icon displayed, press and hold the DISPLAY/HOLD TO MUTE button for FIVE seconds until the speaker-NOT icon flashes off and on. The unit will mute the alarm all the time except for faults. DISPLAY AVR ON BATT LOAD ON LINE CLICK When you press the DISPLAY button the third time, the ESTIMATED RUN TIME IN MINUTES is displayed. In this example, the value is 18 minutes. ON LINE DISPLAY LOAD Warning 2 - Battery Backup Overload This warning indicates that there is a backup battery (ONBATT) overload condition. This is indicated by the flashing overload icon. LOAD When AVR is illuminated on the LCD, it indicates that the automatic voltage regulation (AVR) circuitry is in Boost mode. AVR compensates for excessively low voltage conditions without going on battery. In this example, 90 V is displayed. LOW SENSITIVITY IN V LOW ON BATT AVR DISPLA Y ESTIMATED RUN TIME IN MINUTES Sensitivity kW MID HIGH Flashing A typical condition where sensitivity adjustments would be appropriate is with an AC line input, and with the UPS off. Press and hold the power ON/OFF pushbutton in for 10 seconds. The unit will go into "sensitivity programming mode". Use the ON/OFF button to select the LO, MID or HIGH range. LO displays one block, MID is three blocks, and High is five blocks. Sensitivity programming mode is also discussed on Page 3. SENSITIVITY When you press the DISPLAY button a fourth time in ON LINE mode, the LOAD in Watts (W) is displayed, in this example 760 W is displayed. Warning 3 - Online Bad Battery LOAD ON LINE LOAD ON LINE When you press the DISPLAY button a third time the battery backup (ON BATT) output (OUT) voltage (V) is displayed, in this example it is 115 V. ON BATT LOAD This warning indicates that you are in ONLINE mode, and you have a bad battery, indicated by the flashing bad battery icon. IN V DISPLAY W V OUT Flashing When you press the DISPLAY button a fifth time, the online LOAD as a percentage (%) is displayed, in this example it is 82%. Warning 4 - Battery Backup Low Battery LOAD ON LINE LCD Full Time Display Mode LOAD LOW ON BATT When you press the DISPLAY button a fourth time the battery backup (ON BATT) input voltage (IN) is displayed. % LOAD LOAD This warning indicates that the battery is low. This is indicated by the word LOW, and the Battery Capacity indicator bar flashing. V Flashing The LCD can be set to full time display mode by performing the following steps: 1. Ensure the unit is connected to utility input power, and the power on/off switch is turned off (no power is supplied to the output connectors). 2. Press the DISPLAY/HOLD TO MUTE pushbutton, and hold it in for 10 seconds. All five blocks in the Battery Capacity bar will flash off and on, which indicates the unit is in pushbutton programming mode. Note: A rotating selection method is used that allows you to step through the display modes using the DISPLAY/HOLD TO MUTE button until you select the display mode you want. For example, in Power Save mode none of the blocks are lit. If all five of the blocks are lit, it indicates the LCD is in full time mode, and will remain on full time. 3. When you rotate through the selections and reach the display mode you want, press and release the DISPLAY/HOLD TO MUTE button to select the display mode. ON BATT ON BATT Pressing the DISPLAY button a sixth time displays the ON LINE output (OUT) voltage, in this example the value is 110 V. LOAD ON LINE The first example shows an over voltage condition at 149 V. The second example shows a black out, or less than 10 Vac. IN V IN SYSTEM FAULTS Up to nine system faults can be displayed (F01 F09). A note, SEE MANUAL, is provided just below the system fault number. The system faults include: F01 - On-Battery Overload F02 - On-Battery Output Short F03 - On-Battery XCap Overload F04 - Clamp Short F05 - Charger Fault Flashing V OUT When you press the DISPLAY button a fifth time the (ON BATT) input LOAD in Watts (W) is displayed, in this example 760 W is displayed. ON BATT LOAD ESTIMATED RUN TIME IN MINUTES W F06 - Relay Welding F07 - Temperature F08 - Fan Fault F09 - Internal Fault SEE MANUAL Note: If no buttons are pushed, and no operations occur for five seconds, the unit automatically exits pushbutton programming mode. 4. Once you have selected the desired display mode, continue with normal operations. TROUBLESHOOTING Problem Back-UPS will not switch on. SPECIFICATIONS Possible Cause Back-UPS is not connected to the AC power source. Back-UPS circuit breaker "tripped". ORDER REPLACEMENT BATTERY ORDER REPLACEMENT BATTERY 1300 VA 88 to 139 VAC +12% (Boost mode only) 57 to 63 Hz (Autosensing) Stepped Sine Wave 1300 VA: 780 W 1500 VA: 865 W 1300 VA: 16 Hours and 1500 VA: 16 Hours 32o to 104oF 0o to 40oC Corrective Action Ensure the Back-UPS is securely connected to an AC outlet. Disconnect non-essential equipment from the Back-UPS. Reset the circuit breaker. Switch on the Back-UPS, and plug in devices one at a time. If the circuit breaker trips again, disconnect the device that caused the breaker to trip. Connect the battery cartridge (see Connect Battery Cartridge). Consider adjusting the transfer voltage and sensitivity. See Transfer Voltage and Sensitivity Adjustment. Unplug the device from the 'Surge Only' outlet, and move to a 'Battery Backup' outlet. Verify the Back-UPS's plug is fully inserted into the wall, and power is present at the wall outlet by plugging in a known good device. No action is neccessary. Consider adjusting the transfer voltage and sensitivity. Reference Transfer Voltage and Sensitivity Adjustment. Unplug non-essential equipment (printers, scanners, etc) from the Battery Backup outlets, and plug them into 'Surge Only' outlets. Charge the battery cartridge for 16 hours. Back-UPS runtime is reduced until the battery cartridge is fully charged. Refer to Replace Battery Cartridge, and replace the battery cartridge. Refer to Replace Battery Cartridge, and replace the battery cartridge. Move one or more equipment power plugs from Battery Backup outlets to Surge Only outlets. One of nine Internal UPS Fault Messages is displayed: F01 - On-Battery Overload F06 - Relay Welding F02 - On-Battery Output Short F07 - Temperature F03 - On-Battery XCap Overload F08 - Fan Fault F04 - Clamp Short F09 - Internal Fault F05 - Charger Fault Contact APC Technical Support (see Contact Information). Item On-line Input Voltage Range (default settings) Automatic Voltage Regulation (AVR) On-line Frequency Range On-battery Waveshape Maximum Load Typical Recharge Time Operating Temperature Storage Temperature / 1500 VA The battery cartridge typically lasts 3 to 6 years, a shorter period if subjected to frequent outages or elevated temperatures. For the BR1300LCD, BR1500LCD, BX1300LCD and BX1500LCD order part APCRBC109. Please recycle spent battery cartridges. Internal battery is not connected. Utility input voltage quality is out of range. Back-UPS does not power essential equipment during an outage. Back-UPS operates on battery although utility power is provided. Equipment is plugged into a Surge Only outlet. The UPS's plug has partially pulled out of the wall outlet, the wall outlet was turned off, or its circuit breaker tripped. Unit is performing an automatic self test. Utility input voltage is out of range, frequency is out of range, or the waveform is distorted. Back-UPS does not provide expected amount of backup time. Back-UPS is overloaded. Back-UPS battery cartridge discharged due to a recent power outage, and has not had time to recharge. Battery has reached end of life. Replace Battery indicator is on. Overload indicator is on, or flashing. System Fault indicator is on and all other front panel indicators are flashing. Battery has reached end of life. Connected equipment is drawing more power than the Back-UPS can provide. Internal UPS fault. WARRANTY The standard warranty is three (3) years from the date of purchase. APC's standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement unit to the customer. 23o to 113oF -5o to 45oC Operating / Storage Relative Humidity 0 to 95% non-condensing Size (H x W x D) 8.7 inch x 5.1 inch x 13.8 inch 220 mm x 130 mm x 350 mm Weight 1300 VA: 29.7 lbs (13.5 kg) 1500 VA: 30.7 lbs (14.0 kg) Shipping Weight 1300 VA: 33.2 lbs (15.1 kg) 1500 VA: 34.2 lbs (15.6 kg) EMI Classification FCC / DOC Class B Certified On Battery Run-Time Go to: http://www.apc.com/product Approvals TUV C-US, NOM Notice: This device complies with Parts 68 and 15 of the FCC rules.Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. There is a label on the bottom of this equipment that contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company. SERVICE If the Back-UPS arrived damaged, notify the carrier. If the Back-UPS requires service, do not return it to the dealer. The following steps should be taken: 1. 2. 3. Consult the Troubleshooting section to eliminate common problems. If the problem persists, go to http://www.apc.com/support/. If the problem still persists, contact APC Technical Support. · Have the Back-UPS model number, serial number and date of purchase available. Be prepared to troubleshoot the problem with an APC Technical Support representative. If this is not successful, APC will issue a Return Merchandise Authorization (RMA) number and a shipping address. CONTACT INFORMATION Technical Support Internet USA / Canada Mexico Worldwide http://www.apc.com/support http://www.apc.com 1.800.800.4272 292.0253 / 292.0255 +1.401.789.5735 LIMITED WARRANTY TRANSFER VOLTAGE and SENSITIVITY ADJUSTMENT In situations where the Back-UPS or connected equipment appears too sensitive to the input voltage, it may be necessary to adjust the transfer voltage. This is a simple task using the front panel power on/off pushbutton. To adjust the transfer voltage, proceed as follows: 1. Plug the Back-UPS into the utility power source, but do not turn the unit on.The Back-UPS will be in standby mode (there are no indicators lit). 2. Press and hold the front panel on/off switch in for 10 seconds, until all the indicators on the Back-UPS flash to acknowledge it has entered sensitivity programming mode. Release the on/off button, the blocks in the Back-UPS's LOAD bar shown on the LCD indicate it's current sensitivity setting, as described in the table below. Note: The Back-UPS automatically exits programming mode in five seconds if no buttons are pressed, and no operations are run. Reference the table below to determine which sensitivity setting to select. Input Voltage Range (utility operation) 4. To select the Low Sensitivity setting, press and release the ON/OFF switch several times until only the first block in the Load Bar is lit and flashing, then release the switch. 5. To select the Medium Sensitivity setting (the unit's default), press and release the ON/OFF switch until the first three blocks in the Load Bar are lit and flashing, then release the switch. 6. To select the High Sensitivity setting, press and release the ON/OFF switch until all five blocks of the Load Bar are lit and flashing, and then release the switch. 7. If there are no operations for five seconds, the Back-UPS will automatically exit sensitivity programming mode, and the Back-UPS is ready for normal operation. Indicators Flashing 1 (one block of the Load Bar) 2 (three blocks of the Load Bar) 3 (five blocks of the Load Bar) Sensitivity Setting Low Use When 78 to 142 Vac Input voltage is extremely low or extremely high. Not recommended for computer loads. 88 to 139 Vac The Back-UPS frequently goes on battery (ON BATT). 88 to 136 Vac The connected equipment is sensitive to voltage fluctuations. Medium (factory default) High 990-4991 Copyright © 2006 American Power Conversion. All rights reserved. APC and Back-UPS are registered trademarks of American Power Conversion. All other trademarks are the property of their respective owners.

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual APC BACK UPS BR1300LCD.

APC offer a product for which we do not have the user manual? Let us know what you are looking for: user guide, owner's manual, online manual, operating instructions, quick start guide, mounting instructions, schematics, service manual, installation instructions, RTFM.

Diplodocs allows you to download user manual APC BACK UPS BR1300LCD, user guide APC BACK UPS BR1300LCD, instructions APC BACK UPS BR1300LCD, owner's manual APC BACK UPS BR1300LCD, online manual APC BACK UPS BR1300LCD.


APC BACK UPS BR1300LCD, ,
Know our Partners Frequently Asked Questions Contact Diplodocs team Last searches
Last additions
Sitemap
Brands starting with A B C D E F G H I J K L M N O P Q R S T U V W X Y Z #
Copyright © 2005 - 2008 - Diplodocs - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.