User manual CITADEL XR2 - ENGINEERING INFORMATION @@ XR2+ - ENGINEERING INFORMATION - User guide CITADEL XR2 - ENGINEERING INFORMATION @@ XR2+ - ENGINEERING INFORMATION - English - Diplodocs

DISCLAIMER TO DOWNLOAD THE USER GUIDE CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGIN

Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION will begin.

You agree to use the Manual in accordance with the terms and conditions hereafter described.

1. Our service
Diplodocs offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...

2. Access rights
The documents available on this site are and will remain properties of their respective owners. Accessing, downloading or storing a document on this site does not give you any right. You certify accessing and storing only documents for which you regularly acquired rights of use, either by owning the item corresponding to the document, or thanks to a right to broadcast the document, given by the copyright owners.

3. Our responsibility
In any way can't Diplodocs be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Diplodocs, for instance, does not offer a translation service.

4. Checking of use
Once downloaded, you must make sure that the Manual matches the Product for which you intend to use it. You agree to remain entirely responsible for the use you do with the instructions contained in the document, no matter whether damages of losses occur following its use.

5. Your commitment
In compensation for using our service, you certify not to harm Diplodocs by any legal action, and to help Diplodocs by promoting the site or uploading new documents. You acknowledge that Diplodocs does not owe you mandatory results or availability.


Diplodocs explicitly forbids the use of its service by anyone who do not agree with all conditions above. By accepting or downloading the Manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION, you agree to have read the disclaimer, to have understood all of it and to be bond by its terms and conditions.

You either have JavaScript turned off or an old version of Adobe Flash Player
Get the latest Flash Player.

   

DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

We hope that this CITADEL XR2 - ENGINEERING INFORMATION @@ XR2+ - ENGINEERING INFORMATION user guide will be useful to you.

Need help, support, reviews, tips or troubleshooting for your CITADEL XR2 - ENGINEERING INFORMATION @@ XR2+ - ENGINEERING INFORMATION products ?
Discussion, review, tips, troubleshooting issue, problem : search help on CITADEL XR2 - ENGINEERING INFORMATION @@ XR2+ - ENGINEERING INFORMATION product forum.




close

Download user guide, user manual, owner manual and instructions guide
5 600 brands
1 400 000 user's guides
Search a brand
Advanced Search




User manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION

Diplodocs help download the user guide CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION.

  Download the user manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION     
Download the complete
user guide (1080 Ko)
Need help, support, reviews, tips or troubleshooting for your CITADEL XR2 - ENGINEERING INFORMATION @@ XR2+ - ENGINEERING INFORMATION products ?


Preview of the first 3 pages of manual

You either have JavaScript turned off or an old version of Adobe Flash Player
Get the latest Flash Player.
User guide CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION
XR2/ XR2+ Features Power Intruder alarm system Engineering Information RKP PART SET 8z MEM 4 REMOTE 8 6 OUTPUT 5 09 SET ÿ ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 Tamper Attack 8 zones, all programmable for Security, Fire, 24H Fire, PTS or keyswitch applications PA input Tamper input Outputs for Bell and Strobe 4 Access level Codes, User 1, User 2 and Engineer and Duress, all programmable 3 fully selectable part set programs Chime on any zone 8 event memory Programmable timers including bell cut off Walk Test facilities Quick set feature Remote keypad with on board PA and illuminated keys Option for connection of Lighting controllers Options to connect up to four remote keypads / Lighting controllers NVM for protection of engineer programme 6 digital outputs for a wire-in digital communicator, Red Care STU or dialler Service warning indicator, programmable between 100 and 800 set and unset events Battery capacity of up to : 2.1Ah in XR2 enclosure 7Ah in XR2+ enclosure Features 0 5 Chime 1 6 Omit 2 7 Reset 3 8 Prog 4 PA 9 Set Day Power 8SP 403 XR2+ G3 panel with remote LED keypad ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ Power ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 Tamper Attack 0 5 Chime 1 6 Omit 2 7 Reset 3 8 Prog 4 PA 9 Set Day Power Accenta/! mini 8SP 404 XR2 G3 panel with remote LED keypad The above intruder system is designed to comply with the installation requirements of BS 4737 1986/87. This manual provides information on Installation design, panel fixing, wiring, power up and programming of the intruder panel. 4188-694 issue 1_8/01 1 Downloaded from: http://www.guardianalarms.net Engineering information Contents Features - - - - - - - - - - - - - Installation Design - - - - - - - - Fixing - - - - - - - - - - - - - - Wiring the system - - - - - - - - Tamper network - - - - - - - - - Connecting Remote Keypads / Lighting controllers - - - - - - - Fixing the Remote Keypad (RKP) Security zones - - - - - - - - - - Push to set zone - - - - - - - - - Remote keyswitch zone - - - - - Fire zone - - - - - - - - - - - - PA circuit - - - - - - - - - - - - Extension speaker - - - - - - - - Bell Output (External sounder) - - 13V Supply output - - - - - - - - Set - - - - - - - - - - - - - - - Remote signalling Input and Outputs 1 2 3 4 4 5 5 5 6 6 7 7 8 8 9 9 9 11 12 12 13 13 13 13 13 13 14 15 15 15 16 17 18 18 19 19 20 21 22 23 24 25 26 27 31 31 32 Citadel XR2/XR2+ G3 Intruder system Installation Design The purchase of this alarm system represents a major step forward in the protection of the property and its occupants. It is important to plan the installation before proceeding and then follow the procedures and advice contained in this manual. Plan the position of each part of the alarm system and the cable runs. Detectors should be sited with particular regard to the degree of coverage required and the function of each of the zones. All of the system wiring is connected directly to the panel. The panels may be installed near an entry/exit point. Power Filtering of Intruder alarms - - - - - - - - - - - 10 Installation Design Factory set condition - - - - - - - - First Power up - - - - - - - - - - - Mains Connection - - - - - - - - - Testing the system - - - - - - - - - Engineer program mode - - - - - - System indications - - - - - - - - - To enter Engineer program mode - - To Exit Engineer program mode - - To reset panel to Factory set conditions Access Codes - - - - - - - - - - - Programs - - - - - - - - - - - - - Zone Function per Program- - - - - Exit Modes program - - - - - - - - Programs 1,2 and 3- - - - - - - - - Alarm and Walk tests - - - - - - - Communicator tests - - - - - - - - `Flag A' Options - - - - - - - - - - `Flag B' options - - - - - - - - - - Viewing the event log - - - - - - - Zone Type - - - - - - - - - - - - - Zone Attributes - - - - - - - - - - Bell and Service Timers - - - - - - Re-arm and Anticode reset code - - Lighting controller - - - - - - - - - Faults - - - - - - - - - - - - - - - Specification- - - - - - - - - - - - Index - - - - - - - - - - - - - - - Servicing organisation Details - - - Parts - - - - - - - - - - - - - - - Quick Reference - - - - - - - - - - - Accenta/! mini ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 Tamper Attack 0 5 Chime 1 6 Omit 2 7 Reset 3 8 Prog 4 PA 9 Set Day Power Accenta The Remote keypads (RKPs) should be mounted in positions which allows ease of operation for the system users, typically within the entry/exit route close to the final door and the master bedroom. Additional internal sound speakers are recommended, these will provide high volume alarm tones and low volume entry/exit tones. Speakers should be positioned to provide good sound distribution throughout the building and so that the exit tone is audible outside the main entry / exit door. This will enable the system operator to check that the system is setting correctly. Finally note that the total current output of this control system (in alarm condition) is TOTAL 1A when supported by a fully charged battery. Calculate the total current consumption of every part of the system including the panel, remote keypads, bell/sounders, strobes and detectors to ensure that this rating is not exceeded. I 2 4188-694 issue 1_8/01 Citadel XR2/XR2+ G3 Intruder system Depending on which area you live, you may be required, by law to notify the Local Authority and Police of the new security alarm installation. The local authority requirements may differ from area to area, therefore, it is advisable to contact local environmental officer to obtain full details of your area requirements. Engineering information Note: When replacing the PCB align it on the round support pillars to the bottom and allow it to click down past the clips at the top of the case. Refit the transformer wires into the terminal. b. Fit the panel to the wall with suitable fixings. Ensure the wall surface is flat to prevent base distortion. There are cable entry holes provided in the rear of the base and around the outside edges through the thinned out plastic sections which may be cut away as required. The hole provided adjacent to the mains transformer is a dedicated mains cable entry point. Mounting holes LA Fixing Caution: When positioning the control panel ensure that it is located in a dry place away from damp areas. The XR2 G3 enclosure is illustrated here, however the procedures for the XR2+ panel is similar. a. Remove the front cover(s) from the panel. c. Cable entry holes Disconnect the transformer wires from the transformer marked AC terminals on the board. Carefully remove the PCB by gently pushing down the holding clips on the bottom edge of the PCB and withdraw it from the base. Mounting holes Board There are four fuses mounted on the circuit board, all are 20mm quick blow. F1 1.6A - to protect the +ve line of 12V battery F2 1A - to protect the RKP 13V supply F3 1A - to protect the Speaker 13V supply F5 1A - to protect the Bell and Strobe supply As supplied, wire links are fitted across the PA and Tamper terminals to represent a closed circuit. 4188-694 issue 1_8/01 3 Fixing Engineering information L/FAIL +13V 0V FIRE PA ABORT CONF INT SET Citadel XR2/XR2+ G3 Intruder system J3 RKP FUSE 1A SOUND COMMS +13V 0V TAMP F2 J5 VOLUME D18 VR1 13V / SPEAKER BELL/STROBE F5 F3 BATTERY F1 J4 +BATT AC J2 1 2 3 4 5 6 7 8 PA + TAMP +13V 0V - J6 + TA SCB TAMP DB BELL SET STROBE + - 1A 1A 1.6A Factory fitted links Wiring the system Wiring the system Tamper network The Tamper circuit is used to protect all cables and detectors in the system from unauthorised access including the panel and RKP covers. The zone and PA tampers should be series wired and connected to the TAMP terminals. Terminals T & A are for the external bell / sounder tamper. The TAMP terminals at the bottom left of the PCB are for the RKP tampers. Tamper alarms that occur in the Day mode operate internal sounders only. Tamper alarms in Set cause a full alarm condition. Tamper is indicated on the control panel and RKPs by the Tamper indicator. Caution: Always power-down the panel when wiring external circuits, to prevent damage to the panel electronics. Systematically wire and test each circuit: ÿ ÿ Zone, Tamper circuit and PA circuits Finish by wiring any additional extension speaker sounders, external bell/sounder, strobe and the 13V supply. OPTI-CAM Lighting Controller Board COMMS SOUND LD R GND 12V Keypad Board COMMS SOUND TAMP Keypad Board COMMS SOUND Panel TAMP 13V 13V 0V 0V Board RKP FUSE 1A F2 SOUND COMMS +13V 0V Maximum of up to 4 Remote Keypad / OPTI-CAM Lighting Controller combination allowed (See also the instructions supplied with the OPTI CAM lighting controller) TAMP If only one Remote keypad is being used then connect TAMP back to the panel J5 4 4188-694 issue 1_8/01 Citadel XR2/XR2+ G3 Intruder system Engineering information Connecting Remote Keypads / Lighting controllers Note: Ensure there is at least one remote keypad wired to the panel before first power up. A combination of up to four remote keypads and lighting controller can be connected to the panel. The cable length between RKP and panel must not exceed 100m. Security zones Panel Board J2 1 2 3 4 5 6 7 8 PA + TAMP +13V 0V - Terminal block is not supplied PIR Fixing the Remote Keypad (RKP) a. Separate the RKP back plate from the main assembly by slackening the retaining screw and lifting the back clear of the front moulding. For cable entry cut away the required thin wall section around the edges of the back plate. Mount the back plate onto the wall using suitable fixings. The mounting holes are at 60mm centres to allow the back plate to be fixed to a single gang metal box. Bring the cable(s) into the base and wire to the 6 way terminal block on the main assembly. Refit the main assembly to the back plate, ensure wiring does not foul the tamper switch/spring or PCB support pillars. Re-secure the screw in the bottom of the case. Door Contact + Alarm - Tamp Unused zones must be programmed as Unused. b. Door Contact PIR c. d. Note: The panel is not supplied with wire links for unused zones. All unused zones must be programmed out by setting them to disabled using the Zone Type function see page 20. It is recommended that no more than 10 magnetic contacts are connected to the same zone. e. 4188-694 issue 1_8/01 5 Connecting Remote Keypads / Lighting Engineering information Citadel XR2/XR2+ G3 Intruder system Push to set zone Any zone can be wired and configured as a Push to Set input. This can be a standard door bell push located outside the premises. After starting the exit timer the building is vacated. As the switch is then momentaraily closed, a chime tone is produced and the system Sets. Sometimes referred to as `Terminate Set' this facility is mandatory for communicating systems installed to NACOSS guidelines Panel Board J2 1 2 3 4 5 6 7 8 PA + TAMP +13V 0V Remote keyswitch zone Any zone can be wired and programmed as a keyswitch input and used with a remote keyswitch or lock switch. For security reasons it is recommended that a tamper proof switch is used and that the switch wiring is not accessible from outside the premises. Panel Board J2 1 2 3 4 5 6 7 8 PA + TAMP +13V 0V - - Keyswitch Note: A keyswitch can be connected to any zone. The zone must be programmed for keyswitch application. Press to Set Switch Push to set zone Note: The push to set switch can be connected to any zone. The zone must be programmed for PTS application. The keyswitch may be used to Set (open contacts) or Unset (closed contacts) independently of RKPs. However in this situation the keyswitch may have to `catch up' with the system. For example if the system is Set via an RKP and Unset with the keyswitch, it would have to be momentarily turned to its Set position then returned to its Unset position. The keyswitch will always Set program 1. It will also Unset the system or switch off an alarm activation. To Reset after an alarm and return to Day mode, the Reset key on the RKP will have to be pressed. 6 4188-694 issue 1_8/01 Citadel XR2/XR2+ G3 Intruder system Engineering information Fire zone Any zone may be programmed as a fire zone. This will automatically exclude the availability of the zone from programs and normal security applications. Panel Board J2 1 2 3 4 5 6 7 8 PA + TAMP +13V 0V PA circuit Any quantity of normally closed type personal attack button may be wired in series and then connected to the PA circuit. Operational in Day and Set, the PA circuit will cause a full alarm condition when activated. PA is indicated on the control panel or RKP as Attack. Panel Board J2 1 2 3 4 5 6 7 8 PA + TAMP +13V 0V - - Fire detector Note: Fire detector with relay base for output to intruder system. Panic Button There are two types of fire zone, Standard and 24 hour type. The Standard fire zone detects fires only when the system is Set, where as the 24 hour fire zone detects fires all the time and will operate whether the system is Set or Unset. A fire will cause a distinctive internal sounder tone. The external sounders will pulse on and off at 2 second intervals and all RKP indicators will flash the affected zone. Panic Button PA buttons may be fitted near the front door, or in a bedroom. 4188-694 issue 1_8/01 7 Fire zone Engineering information Citadel XR2/XR2+ G3 Intruder system Extension speaker Extension speaker may be connected to the loudspeaker terminals to produce high volume alarm tones and low volume entry / exit fault tones. Panel VOLUME BELL/STROBE Bell Output (External sounder) The bell is usually installed in a high position from where the bell could be seen and heard. Terminal T A D B are for connection to the external bell or sounder. These terminals provide a power/hold-off supply, sounder trigger and tamper circuit to protect the external sounder housing. Panel Board J6 + TA SCB Board F5 13VSPEAKER VR1 F3 J6 + TA SCB STROBE DB BELL SET + - DB BELL SET STROBE BELL/STROBE 1A 1A F5 + - 1A 16 Extension Speaker 16 Extension Speaker Extension speaker Up to two 16 ohm extension speakers may also be wired across the speaker terminals. Mounted in convenient positions within the installation the extension speakers will reproduce all of the alarm tones generated by the control panel. A control marked VOLUME in the centre of the PCB may be used to adjust the low volume entry/exit tones to suit environmental conditions. +STROBE T E A D B Sonade The terminals are summarised as follows: T-Ve tamper return A-Ve supply (0V) D+Ve supply (12V) -Ve Sounder trigger BFor ease of installation, Sonade sounders and modules use the same markings. Where a discrete bell sounder is used, it should be connected to terminals D & B. Terminals T & A are then used for tamper protection for the sounder housing. 8 4188-694 issue 1_8/01 Citadel XR2/XR2+ G3 Intruder system Panel Board BELL/STROBE Engineering information Remote signalling Input and Outputs F5 J6 + - STROBE TA SCB DB BELL SET + - 1A # Terminal block is not supplied These terminals have been provided for connection to remote signalling equipment such as a digital communicator, Red Care STU or speech dialler. # +STROBE T E A D B +STROBE T E A D B Note: The operating polarity of the Communicator output terminals are programmable. L/FAIL This is a telephone line fail input which is held at approximately 6V by the panel circuitry. The input is activated when pulled to 0V by the telephone line fault output of the communicator. This is usually a voltage free relay or open collector transistor. Sonade Sonade Where self contained / powered sounders are used, carefully follow the manufacturers instructions, match each of the terminals to those above. Panel J6 + TA SCB When a telephone line fault occurs in the Day mode the panel provides an audible double beep every 10 minutes. This indication is automatically cleared when the fault is removed. A telephone line fault which occurs while the system is Set will not cause an alarm condition but any bell delay which is programmed will be cancelled and any intruder alarm which is triggered will operate instant sounders. 13V 0V These terminals provide a 13V supply for the communicator up to a total load of 200mA. The output is protected by a 250mA thermal fuse. If this fuse operates it may be reset by removing the load and allowing a few seconds for it to recover. OUTPUT PORT By default these outputs are programmed as active low output. They are held at 13V and fall to 0V when active, it can source or sink 10mA. The output polarity can be programmed. These outputs would normally be connected directly to the input channels of wire in type communicators and STUs. DB BELL SET STROBE BELL/STROBE Board F5 + - 1A COM Rtn Signal Citadel Defender 13V Supply output The 13V output is to power detectors which require a voltage supply (PIR detectors etc). The supply is present at all times and may be used to supply a total load of 350mA. Set The output, marked SET is used with latching detectors. The output becomes positive on correct Set of the system and is removed at the commencement of entry time or entry of the valid user code. 4188-694 issue 1_8/01 Supply Hold Off + -Ve Strobe Trigger - Supply Hold Off - Siren Trigger - 9 13V Supply output Engineering information Alternatively each output can be used to drive a relay(coil resistance > 1200 ) connected between the output terminal and the 13V supply terminal. The relay will energise when the output port operates. It is recommended that a protection diode is used in parallel with the relay coil. FIRE The fire output operates when the fire zone is triggered. Remote signalling Input and Outputs PA The PA output operates when a PA alarm is triggered or a duress code is used. INT The intruder output is operated when an intruder condition is triggered whilst the system is set. SET The Set output operates whenever the system becomes set and is used to indicate opening and closing. ABORT Operates when an intruder alarm condition is switched off. CONF The confirmed alarm output operates when 2 independent zones are activated during the same alarm condition. Important Notes a. Each output has been configured as active low and will normally require the EPROM or NVM for the communicator or STU to be programmed as active low or positive removed. However there may be differences between some pieces of equipment and some Alarm Receiving Centres (ARCs). b. Where the communicator is powered from an external source, not the panel and the outputs are being used without relays, the panel and external power supply will require a commoned negative supply rail. If the communicator is not fitted inside the panel and abort is being used, care should be taken to ensure that the abort connection cannot be damaged or severed as this could cause the Citadel XR2/XR2+ G3 Intruder system ARC to incorrectly filter an alarm signal. d. It is very important that communicating systems are fully tested and that all signals are correctly received at the ARC when the system is installed and serviced. Filtering of Intruder alarms A condition of most police Force Policies and under the guidance of NACOSS NACP 14 (Code of Practice for intruder Alarm Systems Signalling to Alarm Receiving Centres) is that all intruder alarm signals received by an Alarm Receiving Centre (ARC) must be filtered to establish their validity before passing to the police. The exact method of filtering should be decided according to the regional Police Force Policy and ARC procedures. In general, the panels offer the following methods which could be used to filter an alarm. Set/Unset A Set or Unset signal which is received by the ARC at around the same time as an intruder signal can be used to filter the alarm. Abort Output The abort output operates whenever a user code is entered or a keyswitch is used to switch off an intruder alarm condition. When an abort signal is received by ARC at or around the same time as an intruder signal, the alarm can be filtered. Restore of the Intruder Output The intruder alarm output is restored to 12V whenever a user code is entered or a keyswitch is used to switch off an intruder alarm condition. Where an intruder alarm is shortly followed by a restore at the ARC, this can be used to filter the alarm. c. 10 4188-694 issue 1_8/01 Citadel XR2/XR2+ G3 Intruder system Engineering information Factory set condition User code 1 - User code 2 - Duress Code - Engineer Code Bell Duration Bell Delay - - Program 1 Zone 1 - - Zone 2 - - Zones 3...8 Exit time- Entry - - Exit mode Program 2 Zone1 - - Zone 2 - - Zone 3...8 Exit time- Entry time Exit mode Program 3 Zone 1 - Zone 2 - Zone3...8 Exit timeEntry time Exit mode 0123 Not programmed Not programmed 9999 20 minutes No delay Flag A Silent PA - - - - - - RKP PA Enable - - - Engineer Reset- - - - Anti Code Reset - - - Door bell on push to set Single key setting - - Strobe on setting - - - External bell on Fire - Flag B Communicator Output active high - - - - - Line Fail active high - - - - - User Reset PA - - - User Reset Fire - - - Program 1 to report - Program 2 to report - Program 3 to report - Rearm counter - - - Service counter - - - Site Code - - - - - - Light Controller Light Threshold Light Hold Time Light Channel 1 Light Channel 2 Light Channel 3 Light Channel 4 Light Channel 5 Light Channel 6 Light Channel 7 Light Channel 8 - - - - - - - Timed Time Inhibited Immediate 30seconds 30seconds timed - - No Yes No No No No No No - - - - No (active low) No (active low) No No Yes Yes Yes 3 (re-arms) Off 00 Factory set condition - - - - - - Timed Time inhibited Immediate 30seconds 30seconds Disabled - - - - - - - Timed Time Inhibited Immediate 30seconds 30seconds Disabled Zones 1...8 None programmed None programmed None programmed None programmed None programmed None programmed 300mS ALL zones Security Zones - - - Standard Fire zones 24 hour Fire zones - Push to set zones - - Keyswitch zones - - Double Knock zones Omit prevent zones- Zone debounce period - - - - - 50% 30 seconds No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned 4188-694 issue 1_8/01 11 Engineering information Citadel XR2/XR2+ G3 Intruder system Note: The panel is not supplied with wire links for unused zones. All unused zones must be programmed out by setting them to disabled using the Zone Type function see page 20. First Power up To power up for the first time: a. Check that the factory fitted links are connected to terminals PA, TAMP and T-A. Fit the battery wires to the BATT terminals on the PCB, Red to + and Black to -. Panel BATTERY b. Mains Connection The mains power should be connected using a 3 core cable of not less than 0.75mm sq. from a fused spur to the mains connector inside the control panel. The 2A fused spur must be located close to the control panel. Dedicated mains supply from consumer unit. F1 Board J4 +BATT AC 1.6A (red) + Black - N E L 125mA Fuse 2A Fused Spur unit Panel BATTERY F1 Board J4 +BATT AC First Power up 12V battery Transformer c. On connecting the battery the system will now go into alarm condition and Tamper is indicated Tamper 1.6A and there is an audible (red) + Black - N E L 125mA Fuse Transformer d. Alarm. indication. Fit the cover to hold down the tamper spring at the bottom centre of the PCB. 12V battery e. Enter the user code: 0 1 2 3 (factory set at 0123). The alarm condition will cease and the system will go to Day mode . Immediately enter the engineer code Prog Day Note: The mains supply must be connected by a technically competent person and according to current IEE regulations. Caution: To avoid the risk of electrical shock you must always totally isolate the mains supply before opening the control panel cover(s). Mains Input Fuse rating: 125mA, 250V type T (anti surge) and of a type approved to IEC 127 part 2 sheet III. On connecting the mains supply to the panel the power indicator is lit. Power f. . The system is now in Engineer program mode and can be programmed. Note the Tamper 9 9 9 9 ÿ Tamper indicator is lit. 12 4188-694 issue 1_8/01 Citadel XR2/XR2+ G3 Intruder system Engineering information Testing the system Complete the wiring of the system and then: System indications Day Power ÿ ÿ ÿ ÿ - Unset system indication Fully test the system and ensure it is fault free. Fully program the system. Fill in the installation log at the back of the manual and retain if for future reference. Finally explain the operation of the system to the end user. The Operating Instructions are attached to the centre of this manual. Detach them and leave them with the user. Power - Set system indication


CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION, , Safety & Domotic.

Detailed instructions for use are in the User's Guide.

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION.

CITADEL offer a product for which we do not have the user manual? Let us know what you are looking for: user manual, user guide, instructions, owner's manual, online manual, user's manual, users manual, users guide, owner manual, owners manual, user's guide, handbook, instructions for use, instruction manual, operation manual, operating instructions, installation guide, quick start guide, quikstart guide, getting started, installation instructions, installation guide,mounting instruction, assembly instrucions, fixing instructions, use instruction, schematics, operating manual, feature sheet, data sheet, booklet, service manual, use and care guide, installation manual, installation software, RTFM.

Diplodocs allows you to download user manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION, user guide CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION, instructions CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION, owner's manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION, online manual CITADEL XR2 - ENGINEERING INFORMATION , CITADEL XR2+ - ENGINEERING INFORMATION.


Access web reviews
Copyright © 2005 - 2008 - Diplodocs - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.