Detailed instructions for use are in the User's Guide.
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLuxTM Lighting System Operations Guide
This document was prepared and written by the Technical Documentation department at:
Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 1-888-CRESTRON
All brand names, product names and trademarks are the property of their respective owners. ©2006 Crestron Electronics, Inc.
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
iLuxTM Lighting System
Contents
iLuxTM Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M 1
Introduction ............................................................................................................................... 1 Features and Functions ................................................................................................ 1 Specifications .............................................................................................................. 4 Physical Description.................................................................................................... 4 Industry Compliance ................................................................................................... 8 Setup .......................................................................................................................................... 9 Network Wiring........................................................................................................... 9 Identity Code ............................................................................................................... 9 Installation ................................................................................................................... 9 Hardware Hookup ..................................................................................................... 11 Adding External Power Supplies............................................................................... 11 Configuring the CLS-C6.......................................................................................................... 12 Configuring With Front Panel Controls .................................................................... 12 Configuring With iLux Designer............................................................................... 21 Console Command Settings ...................................................................................... 23 Replacing the Function Button Label........................................................................ 24 Programming Software ............................................................................................................ 26 Earliest Version Software Requirements for the PC ................................................. 26 Programming with Crestron SystemBuilder/D3 Pro ................................................. 26 Programming with SIMPL Windows ........................................................................ 27 Example Program ...................................................................................................... 28 Uploading and Upgrading........................................................................................................ 29 Establishing Communication..................................................................................... 29 Programs and Firmware ............................................................................................ 29 Operation ................................................................................................................................. 31 Button Types ............................................................................................................. 31 IR Receiver................................................................................................................ 33 Occupancy Sensing ................................................................................................... 34 Problem Solving ...................................................................................................................... 37 Troubleshooting......................................................................................................... 37 Check Network Wiring.............................................................................................. 37 Reference Documents................................................................................................ 38 Further Inquiries ........................................................................................................ 38 Future Updates .......................................................................................................... 39 Appendix A: Supported Devices ............................................................................................. 40 Keypads..................................................................................................................... 40 Shade Controllers ...................................................................................................... 40 Appendix B: Console Commands............................................................................................ 41 Appendix C: Factory Default Values....................................................................................... 45 Appendix D: Button Functions ................................................................................................ 46 Software License Agreement................................................................................................... 53 Return and Warranty Policies .................................................................................................. 55 Merchandise Returns / Repair Service ...................................................................... 55 CRESTRON Limited Warranty................................................................................. 55
Operations Guide - DOC. 6347B
Contents · i
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
iLuxTM Lighting System
iLuxTM Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M
Introduction
Features and Functions
· · · · · · · · · · · · · · Wall-mounted integrated lighting and shade control Six channels of dimming or switching Six groups of shade or drape control Linkable for up to 54 lighting channels and 54 shade groups Up to 16 user-settable scenes | Large ON and OFF buttons Seven configurable "rocker" buttons with customizable label strip Flip-up front cover reveals setup controls and programming port Six bargraphs show lighting levels and shade positions Easy setup from front panel or iLux Designer software Built-in motion detector (CLS/CLSI-C6M) | Optional IR remote Supports multipoint control using up to 16 keypads Master air-gap relay | 230V AC version available Integrates with 2-Series control systems via Cresnet Available in almond, black, or white
Six Channel Dimming
The CLS-C6 features six channels of dimming for incandescent, magnetic lowvoltage, neon/cold cathode, and two-wire dimmable fluorescent loads. Each channel can also support switching of many non-dimmable lighting loads. Each channel will handle up to 800 watts individually, with a total rating for the complete unit of 1920 watts at 120 VAC for CLS-C6/C6M (2300 watts at 230 VAC for CLSI-C6/C6M).
Operations Guide - DOC. 6347B
iLuxTM Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M · 1
iLuxTM Lighting System
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
Six Group Shade Control
Using Crestron's networked shade and drape controllers (sold separately), the CLS-C6 enables versatile control of a roomful of motorized window treatments, screens, and lifts in up to six shade groups. Each controller is connected to the CLS-C6 via the four-wire Cresnet bus.
Versatile Front Panel Controls
The deceptively clean front panel actually affords an extensive amount of control and customization to suit each unique room application. Large ON and OFF buttons provide instant access to the "On" and "All Off" scenes, while the six main buttons can be set up to recall additional scene presets, adjust shades, or perform a host of other functions. The buttons' "rocker" action enables intuitive control for adjusting lighting levels and shade positions. An additional "Up/Down" button is configurable for a variety of functions, including use as a master lighting or shade control, or as a "shift" button to expand the capabilities of the six main buttons. With each new scene selection, window shades reposition and lights fade elegantly to their new settings. The selected scene is indicated by a white LED beside each button, and the customizable label strip allows each button to be clearly labeled using Crestron Engraver software. Dimming levels and shade positions are displayed graphically on six green LED bargraphs accessible behind the flip-up front cover. Additional controls and a numeric display hidden beneath the cover enable setup without requiring a PC. Enhanced customization is provided via the PC programming port using iLux Designer software.
Built-in Motion Detector (CLS/CLSI-C6M)
The CLS/CLSI-C6M model provides the addition of a built-in infrared motion detector, enabling automated control based on room occupancy. Lights can be programmed to turn on and shades open automatically when someone enters the room, or turn off and close when the room is left empty. Remote motion detectors are also available to expand the coverage of the CLS/CLSI-C6M, or add occupancy sensing capability to the CLS-C6 units.
IR Remote Control
The CLS-C6 units are equipped with an onboard IR receiver to allow for wireless remote control using Crestron's optional infrared remote control (sold separately).
Multipoint Keypad Control
Up to 16 Crestron keypads (sold separately) may be connected to a single CLS-C6, providing versatile multipoint control for rooms with several entrances or work areas.
Multi-Unit Expansion
A single CLS-C6 master will support up to eight additional CLS-C6s, enabling systems of up to 54 lighting channels and 54 shade groups. Scene recall, master dimming, and occupancy status are shared between all the CLS-C6 units. Each individual unit can still support a complete assortment of local devices including keypads, shade controllers, and sensors.
2
· iLuxTM Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M
Operations Guide - DOC. 6347B
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
Control System Integration
iLuxTM Lighting System
The CLS-C6 actually features two separate Cresnet control networks, one for local devices and one for connection to a 2-Series control system. Connecting the CLS-C6 to a control system allows its functions to be controlled from touchpanels, RF wireless remotes, and even computers, supporting extensive flexibility for remote control and integration with other devices and systems. Additional functions such as on-the-fly room combining and activating operations based on a real-time clock are also made possible by connecting the CLS-C6 to a control system. Connecting to an Ethernet-networked control system provides a gateway to larger applications such as integration with facility-wide lighting, HVAC, security, and remote monitoring via Crestron RoomView® Help Desk software as well as thirdparty SNMP software.
Operations Guide - DOC. 6347B
iLuxTM Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M · 3
iLuxTM Lighting System
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
Specifications
The following table provides specifications for the CLS-C6.
CLS-C6 Specifications
SPECIFICATION Load Ratings CLS-C6/C6M Max load per channel : Min load per channel Max load per unit: CLSI-C6/C6M Max load per channel : Min load per channel Max load per unit: Power Requirements Default Net ID Control System Update Files Minimum 2-Series Control System Load Types
1, 2
DETAILS
800 W/VA (6.7 Amps @ 120 VAC) 15 W/VA (0.125 Amps @ 120 VAC) 1920 W/VA (16 Amps @ 120 VAC) 800 W/VA (3.5 Amps @ 230 VAC) 25 W/VA (0.108 Amps @ 230 VAC) 2300 W/VA (10 Amps @ 230 VAC) CLS-C6 Line Power, 100 Â127 VAC, 50 / 60Hz CLSI-C6 Line Power, 220 Â 240 VAC, 50 / 60Hz 1F Version 2.004.CUZ or later Incandescent, magnetic low voltage, neon/cold cathode, dimmable 2-wire fluorescent, and non-dim lighting (also: electronic low voltage, 3-wire and 3 4-wire fluorescent ) 36 kHz Requires Crestron IR remote (sold separately).
IR Receiver Reception Frequency Motion Detector (CLS/CLSI-C6M only Type Range Firmware Environmental Temperature Humidity Overall Dimensions: Height Width Depth Weight 1. 2. 3.
Infrared 20 to 30 feet at 4-foot elevation (6 to 9 meters at 1.2 meter elevation) clsi-c6_clsi-c6m_1.01.02.upg or later 32° to 104°F (0° to 40°C) 10% to 90% RH (non-condensing) 4.48 in 8.89 in 2.46 in 2.59 in (11.38 cm) (22.58 cm) (6.25 cm) for CLS/CLSI-C6 (6.58 cm) for CLS/CLSI-C6M
1.43 lbs (0.65 kg)
The latest versions can be obtained from the Crestron website. Refer to NOTE after last footnote. Crestron 2-Series control systems include the AV2 and PRO2. Consult the lates ...