Sentry Digital Panel Indicator
Universal Input Panel Indicator for Temperature & Process Measurement
Setup Guide
Sentry Digital Panel Indicator
Setup Guide
Contents
Introduction......................................................................................................2 Installation........................................................................................................3 Connections .....................................................................................................5 Connecting the Sensor.....................................................................................6 Powering the Instrument .................................................................................7 Operator Functions..........................................................................................8 The Setup Menus.............................................................................................9 Configuration Menu Map............................................................................. 12 Menu Options ............................................................................................... 14 Messages....................................................................................................... 17
20-5110 Issue B
1
Sentry Digital Panel Indicator
Setup Guide
Introduction
This Setup Guide describes how to install and configure your instrument. This instrument is marked with the international hazard symbol. It is important to read this Setup Guide before installing or commissioning your panel meter as it contains important information relating to safety and Electromagnetic Compatibility EMC. The instrument provides the following features as standard:
· · · · ·
Universal input for mV, mA, volt, thermocouple, RTD and resistance. 1 configurable alarm with relay output. 4 digit bright LED display. Transducer/transmitter supplies. <110mm behind panel depth (or 100mm without any options fitted).
The instrument provides the following features as options:
· · ·
Isolated 4 - 20mA scaleable retransmission output. Up to 2 additional alarms with relay outputs. Front panel keypad with function keys.
2
20-5110 Issue B
Sentry Digital Panel Indicator
Setup Guide
Installation
To install your instrument, you will need to carry out the following steps:
·
· ·
Apply the engineering units label to the right-hand side of the display panel. A sheet of labels covering the most commonly used engineering units is supplied with all units. If the unit you require is not on the sheet, a blank label is provided on which you can use LETRASETTM. Install the instrument into a panel. Make connections to the instrument.
PLEASE NOTE: · Ensure that the power to the instrument is switched off before carrying out any installation or maintenance work. · It is recommended that all connections to the terminals are made using ferrules to afford greater reliability and to prevent short circuits between adjacent terminals. · Avoid installing the instrument close to switch gear, contactors or motor starters. · Do not place signal and power supply wiring in the same loom. · Use screened cables or wires for all signal/sensor leads with screen earthed at one point only.
Panel Mounting
The instrument is supplied with an installation kit consisting of a mounting clamp, a panel sealing gasket and terminal connectors. Ensure that there is sufficient space behind the instrument panel - the instrument requires a depth of 100mm (110mm when any options are fitted) plus enough space to allow safe routing of cables. To install the instrument: 1. Make panel cut-out with the dimensions as shown overleaf. Panel thickness from 1.5mm to 9.5mm can be accommodated.
20-5110 Issue B
3
Sentry Digital Panel Indicator
Setup Guide
2.
Fit the rubber seal by slipping it over the unit from the rear of the box and pushing it forwards until it sits behind the front lip of the unit. Insert the instrument into the panel from the front, pushing it through as far as the front lip, to ensure correct seating of the rubber seal between the panel and the unit. Working from behind the panel, take the mounting clamp, slide over the rear of the instrument and push forwards. Continue to push the clip forward until the ratchet operates and the clamp is sufficiently compressed to apply adequate pressure on the panel.
3.
4. 5.
4
20-5110 Issue B
Sentry Digital Panel Indicator
Setup Guide
Connections
The diagram below shows the rear panel terminal connection arrangement.
Rear Panel Terminal Connections
Ensure the power supply is connected to Terminals 1 & 2 (marked N & L).
20-5110 Issue B
5
Sentry Digital Panel Indicator
Setup Guide
Connecting the Sensor
Thermocouple/mV Resistance & RTD Measurements
Current (±20mA)
2-wire 20mA Transmitter
Voltage Measurement
Bridge Measurement
Potentiometer
10V Transducer Supply
6
20-5110 Issue B
Sentry Digital Panel Indicator
Setup Guide
Powering the Instrument
The instrument is designed to operate from an AC supply with voltages in the range 90 - 265V AC 50/60Hz mains supply with a maximum power consumption of 8VA when all outputs are fully loaded and the display has all segments illuminated. WARNING - The instrument is designed for installation in an enclosure which provides adequate protection against electric shock. Access to power terminals should be restricted to authorised skilled personnel only. Application of supply voltages higher than those for which the instrument is intended may compromise safety and cause permanent damage. The diagram below shows how the instrument should be connected to the mains supply. Isolation should be provided by a double pole switch and a time-delay 200mA fuse.
Recommended Mains Supply Connections
20-5110 Issue B
7
Sentry Digital Panel Indicator
Setup Guide
Operator Functions
These functions are only available on units which have the front panel push buttons.
Operator/Configuration Mode - Key Functions
From the normal runtime display: Enter - Accesses the setup menus. Next - Scrolls forward through the setup menus. Up - Function Key 1 (see page 16).
Down - Accesses the alarm setpoint(s). Use the Next viewing and the Enter Key for editing. Star - Function Key 2 (see page 16).
Key for
NOTE: Units which have the front panel push buttons are externally configurable. Units which do not have front panel push buttons are internally configurable (see page 9).
8
20-5110 Issue B
Sentry Digital Panel Indicator
Setup Guide
The Setup Menus
Next Behind the Front Panel
Enter
The instrument uses a single level menu structure. The menu system lists parameters (eg. inPt, unit, dP, etc.), each of which leads to a list of configurable instrument options (eg. the parameter inPt leads to the options mV, mA, VoLt etc.). To enter the setup menus: 1. Remove the front cover by pushing the extraction tool into the gap below the bezel and then pulling the tool forward to unclip the bezel as shown in the diagram below.
Removing the Bezel with the Extraction Tool 20-5110 Issue B 9
Sentry Digital Panel Indicator
Setup Guide
2. 3. 4. 5. 6. 7. 8.
Press and hold down the Enter Key for approximately 3 seconds until the display begins to flash. Press the Next Key and the flashing display should be replaced with the message inPt (the first menu parameter). To cycle through the menu parameters, press the Next Key repeatedly. To view a menu parameter, press the Enter Key and the current option for that parameter will be displayed. To cycle through all of the available options for a parameter, press the Next Key. Press the Enter Key to select the required option. a)
Editing a Setting
Some parameters are setup by selecting from a list of options o o (eg. the parameter unit has 3 options: C, F and EnG). The following example will show you how to edit a parameter. We will change the decimal places (labelled dP) from 1 to 2.
· · · · · · ·
With the unit displaying the measured value, press and hold down the Enter Key for approximately 3 seconds until the display begins to flash. Press the Next Key and the flashing display should be replaced with the message inPt (the first menu parameter). Press the Next Key repeatedly until dP is displayed. Press the Enter Key and nnn.n will be displayed. Press the Next Key and the decimal point will move and nn.nn will be displayed. Press the Enter Key to save this setting and exit. When the Enter Key is pressed, the display will return to the menu parameter, ie. dP. Press the Next Key repeatedly to scroll through the rest of the menu parameters until the measured value display is restored. 20-5110 Issue B
10
Sentry Digital Panel Indicator
Setup Guide
b)
Editing a Value
Other parameters are changed by editing a value (eg. the parameter HdSP has a default numeric value of [100.0]). Press the Next Key to edit the flashing digit and the Enter Key to select the next digit for editing. The following example will show you how to edit a numeric value. We will change the high display value (labelled HdSP).
· · · · · · · · · ·
·
With the unit displaying the measured value, press and hold down the Enter Key for approximately 3 seconds until the display begins to flash. Press the Next Key and the flashing display should be replaced with the message inPt (the first menu parameter). Press the Next Key repeatedly until HdSP is displayed. Press the Enter Key and 100.0 will be displayed (with the least significant digit flashing). Press the Next Key to scroll through digit values 0 to 9 and edit the least significant digit. To move to the next most significant digit, press the Enter Key and the digit will flash. Repeat the previous 2 steps until the left most significant digit is flashing. Press the Next Key to scroll through digit values -1, - and 0 to 9. If the value allows the dP position to be moved, the dP will flash. To move the dP position, use the Next Key. Press the Enter Key to save this value and exit. When the Enter Key is pressed and the left most significant digit is flashing, the display will return to the menu parameter, ie. HdSP. Press the Next Key repeatedly to scroll through the rest of the menu parameters until the measured value display is restored.
20-5110 Issue B
11
Sentry Digital Panel Indicator
Setup Guide
Configuration Menu Map
12
20-5110 Issue B
Sentry Digital Panel Indicator
Setup Guide
20-5110 Issue B
13
Sentry Digital Panel Indicator
Setup Guide
Menu Options
Input
Default: mV inPt Allows the input type and range to be defined. There are 12 ranges for temperature measurement available. When a thermosensor range is selected, ie. J, K, t, r, S, n or RTD, the instrument will automatically set the appropriate scaling in oC.
Engineering Units
Default: Eng unit Allows the user to define the units of measurement to be displayed o o in C, F and Eng (linear engineering units).
Default: 1 dP Defines the position of the decimal point for the display; 0 or 1 for thermocouples/RTD and 0 to 3 for process inputs.
Decimal Position
High and Low Display Values Default: Low = 000.0, high = 100.0
HdSP LdSP The low display value LdSP is used for scaling purposes when combined with the other scaling parameters L-iP, HdSP, and H-iP. These 4 parameters can scale the measured input to any engineering units as long as the relationship between the displayed units is linear. LdSP is used to define the value to be displayed for an input defined by L-iP. HdSP is used to define the value to be displayed for an input defined by H-iP.
High and Low Input Values
H-iP L-iP Correspond to the signal output values from the sensor which will cause the instrument to display the values set as LdSP and HdSP. L-iP and H-iP can be input in mV, V, mA etc. VAL rEAd There are 2 methods of setting the low and high input values, either by manually entering a signal value using the VAL option or by sampling the sensor output using the rEAd option. Values entered manually are entered in the same way as other numeric values (see Editing a Value page 11). The value to be entered will usually be supplied with the data accompanying your sensor. However, if it is not available, the output from the sensor may be rEAd from an external 14 20-5110 Issue B
Sentry Digital Panel Indicator
Setup Guide
source by the instrument. When performing a rEAd input as part of the scaling process, the sensor must have the corresponding physical value applied. This may be pressure, weight, temperature etc. The instrument will sample the output from the sensor and save this as the L-ip and H-iP scaling parameters. A example of scaling: 0 - 100 mV = 0 -1000 (psi) LdSP = 0 L-iP = 0 (mV) HdSP = 1000 H-ip = 100.0 (mV)
Display Filtering
Default: 000 Filt This parameter is used to apply a digital filter to the display value. The filter is defined in seconds which approximate to the time constant. This parameter would be used to damp out any eff ...