SK-6324 Basic Operating Instructions P/N 151119 Rev. A These instructions must be framed and displayed next to the SK-6324 panel in accordance with NFPA 72 fire code for Local Fire Alarm Systems.
LED (Color)
AC POWER (green)
Function
ON = Good AC OFF = Low AC trouble condition and it was acknowledged FLASHING = Unacknowledged AC Low trouble condition ON = System trouble OFF = System OK FLASHING = At least one serial device is in trouble DOUBLE FLASHING = Two types of serial devices are in trouble. ON = Walk test is in progress OFF = Walk test is off. FLASHING = Walk test is on and at least one zone is not ready
Comments
If flashing, press the ACK button to acknowledge the condition.
GENERAL TROUBLE (yellow)
WALK TEST (yellow)
Allow approximately 47 seconds between detector tests. In walk test, when a detector is tripped, it will cause an alarm for two seconds, then the control panel will drop power to the circuit for seven seconds to reset the detector. Then an additional 38 seconds is needed to restore the detector. If verification is used, the time between detector test will be about 2 minutes and 30 seconds. When condition that caused audible activation clears, this condition will clear automatically. Note: Silencing an alarm will cause a general trouble condition. If flashing, press the ACK button to acknowledge the condition.
SYSTEM SILENCED (yellow)
ON = System audible output has been silenced OFF = Nothing silenced FLASHING = Partially silenced ON = Ground fault condition exists and was acknowledged OFF = No fault FLASHING = A ground fault condition detected ON = Battery low condition that has been acknowledged OFF = Good battery condition FLASHING = Battery low condition ON = Zone in alarm which has been acknowledged OFF = No Alarm FLASHING = Zone in alarm has not yet been acknowledged ON = Zone has a supervisory condition which has been acknowledged (selfrestoring condition) OFF = No supervisory condition exists FLASHING = Supervisory trouble detected on that zone that has not yet been acknowledged
GROUND FAULT (yellow)
LOW BATTERY (yellow)
If flashing, press the ACK button to acknowledge the condition.
ZONE 1 Through ZONE 6
ALARM (red)
If flashing, press the ACK button to acknowledge the condition.
Cut Along the Dotted Line
SUPERVISORY (yellow)
If flashing, press the ACK button to acknowledge the condition.
TROUBLE (yellow) ON = Zone has a trouble condition which has been acknowledged OFF = No zone trouble FLASHING = Zone has a trouble condition not yet acknowledged DOUBLE FLASHING = Zone was disabled CLEAN ME FLASHING = Indicates that the smoke detector needs cleaning
If flashing, press the ACK button to acknowledge the condition.
A "Clean Me Flash" is a flash with a long LED "on" Time and a short LED "off" time indicating that the smoke detector needs cleaning. Applies only to smoke detectors with the CLEAN ME feature. The "Clean Me" flash starts after the trouble condition has been acknowledge.
NAC 1 Through NAC 3
ACTIVE (yellow)
ON = NAC is active during an alarm OFF = NAC is not active during alarm If flashing, press the ACK button to acknowledge the condition.
TROUBLE (yellow) ON = NAC has a trouble condition and was acknowledged OFF = No trouble condition FLASHING = NAC is in trouble DOUBLE FLASHING = Circuit was disabled
Operation
Disable notification appliance circuit. To re-enable the circuit, press [NAC DISABLE] again. Disable a zone To re-enable the circuit, press [ZONE DISABLE] again. Begin Walk Test End Walk Test (The test ends automatically after 10 minutes of no system activity.) Acknowledge condition (alarm, supervisory, trouble) Silence Panel Perform system reset To send a DACT test to your central station. To reset the DACT.
Keystrokes
Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm condition. Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm or supervisory condition. Press [WALK TEST]. Walk Test LED turns on. Note: Walk test will not activate if the control panel has a trouble, alarm, or supervisory condition. Press [WALK TEST]. NOTE: The Walk Test feature is not operational during an alarm, supervisory or any system trouble condition. Press [ACK]. The corresponding LED will change from blinking to steady for the duration of the condition. Except for CLEAN ME trouble indications. Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits that have been configured as "silenceable". Press [RESET]. Resets alarms, supervisories, troubles and all LEDs. Press the [DIALER TEST] button. Press the [DIALER RESET] button.